Pressure transmitters and gauges are often installed with impulse lines. Image courtesy Yokogawa |
A way to aid pressure sensing instruments in situations where direct contact must be avoided is by using a filled impulse line. An impulse line extends from a process pipe of vessel to a pressure measurement instrument or sensor. The line can have a diaphragm barrier that isolates the process fluid from the line, or the line can be open to the process. There are best practices that should be followed in the design and installation of an impulse line to assure that the line provides a useful transmission of the process pressure to the sensor and whatever degree of isolation or protection is needed remains in effect.
The filled impulse line functions via the addition of a non-harmful, neutral fluid to the impulse line. The neutral fluid acts as a barrier and a bridge, allowing the pressure sensing instrument to measure the pressure of the potentially harmful process fluid without direct contact. An example of this technique being employed is adding glycerin as a neutral fluid to an impulse line below a water pipe.
Glycerin’s freeze point is lower than water’s, meaning glycerin can withstand lower temperatures before freezing. The impulse line connected to the water pipe may freeze in process environments where the weather is exceptionally cold, since the impulse line will not be flowing in the same way as the water pipe. Since glycerin has a greater density and a lower freezing point, the glycerin will remain static inside the impulse line and protect the line from hazardous conditions.
The use of an isolating diaphragm negates the need for certain considerations of fill fluid density, piping layout, and the need to create an arrangement that holds the fill fluid in place within the impulse line. System pressure will be transferred across the diaphragm from the process fluid to the fill fluid, then to the pressure sensor. It is important to utilize fluids and piping arrangements that do not affect the accurate transference of the process pressure. Any impact related to the impulse line assembly must be determined, and appropriate calibration offset applied to the pressure sensor reading.
An essential design element of a filled impulse line without an isolating diaphragm is that the fill fluid must be compatible with the process fluid, meaning there can be no chemical reactivity between the two. Additionally, the two fluids should be incapable of mixing no matter how much of each fluid is involved in the combination. Even with isolating diaphragms employed, fluid harmony should still be considered because a diaphragm could potentially loose its seal. If such a break were to occur, the fluids used in filled impulse lines may contact the process fluid, with an impact that should be clearly understood through a careful evaluation.
Share your pressure measurement requirements and challenges with experienced application specialists, combining your own process knowledge and experience with their technical expertise to develop an effective solution.